  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 95
3 - 62
Data Inquiry
Use the Data Inquiry to request the current value for Parameters (i.e., Control
Parameters or Monitor Parameters).
Table 3-33 Data Inquiry - Host Transmission
Character # 1 2 3 4 5 6 7 8 9 10 11 12
DEV # DEV # MSG PAR # PAR # DATA DATA DATA DATA DATA
DESC STX 10s 1s TYPE 10s 1s 1000s 100s 10s 1s FORM ETX
ASCII STX 0-9 0-9 2 0-9 0-9 0 0 0 0 0 ETX
The following is a description of the Data Inquiry - Host Transmission Characters.
Character 1 - STX:
This is the first character in the character string. None of the other characters will
be recognized without this character prefix. Always use the ASCII “STX” character;
it enables the ML–Trims receive buffer.
Characters 2, 3 - Device #:
These characters are the access address of the ML–Trim. This number identifies
individual ML–Trims on a mutltidrop system. The ML–Trim will accept data only if
this number matches the ML–Trim's address (CP-70), with the exception of a “00”
address. The “00” address is universally accepted by all ML–Trims that are on the
RS485 Serial Communications Interface.
Character 4 - Message Type:
This character should always be “2”.